Innovative battery charging container
For smart battery charging - efficient and safe.

Rechargeable lithium-ion batteries have become an integral part of the daily use of power tools and electric gardening equipment such as electric lawn mowers, and the advancement of electromobility in the area of e-scooters, e-scooters and e-bikes is also benefiting from this development.

Our motivation

Lack of an overall solution for safely charging large quantities of batteries

Ladecontainer für Akkus

Compared to conventional battery technologies, the energy content of lithium-ion batteries is many times greater, which can lead to a significant increase in the extent of damage in the event of a fire. Due to the large number of different battery types and the rapidly advancing development in this area, there are currently no public regulations on the storage, charging and provision of lithium batteries, nor are there any generally applicable statements on suitable concepts and overall solutions.

For this reason, Clausohm-Software GmbH, in cooperation with Stadtwerke Düsseldorf, has developed a concept for the safe charging of large quantities of batteries.

Various e-mobility applications (e-scooters, etc.) have already been put into operation since 2020.

We are currently receiving an increasing number of inquiries from green space authorities regarding the switch to electric garden tools and the associated search for safe charging solutions.

We have added applications from Stihl and Husqvarna, for example, to our standard concept for the safe charging of large quantities of batteries.

The assessment and recording of the building law and technical requirements of the loading container was carried out on the basis of the listed regulations, expert opinions and safety concepts.

Overview

Charging container for lithium-ion batteries

Ladecontainer Grafik

What is a battery charging container, what advantages does it offer and for which applications is it suitable?

Kurzer Überblick

  • Begehbares REI / F90 Brandschutzlager mit DIBt-Zulassung
  • Genehmigungsfreie Aufstellung
  • Hochsicher, brandfest und thermisch isoliert
  • Flexible Innen- oder Außenaufstellung
  • Individuell anpassbare Sicherheitskonzepte
  • Intelligentes Lademanagement
  • Überwachung und automatische Abschaltung einzelner Ladevorgänge im Fehlerfall
  • Übermittlung von Fehlern und Alarme
  • Mobile Datenübertragung und Backend
  • Ladekapazitäten von bis zu 384 Akkus gleichzeitig

Vorteile

  • Schützen Sie Ihr Personal und Ihre Sachwerte durch sicheres Laden und Lagern Ihrer Akkus in einem separaten Ladecontainer.
  • Mobilität des Containers macht Sie beim Laden Ihrer Akkus flexibel.
  • Sparen Sie Zeit und Geld (kein Einholen von teuren und langwierigen Genehmigungen).
  • Intelligentes Lademanagement minimiert Lastpeaks und senkt die Kosten für Netzanschluss und Strombezug.
  • Garantierte Transparenz dank automatischer Fehlererkennung und entsprechender Benachrichtigung auf Ihr mobiles Gerät
  • Individuell anpassbar

Einsatzbereiche

  • E-Scooter, E-Roller oder E-Bike Sharing Modelle
  • Gartenbau, Garten- und Landschaftsbau
  • Straßenbaubetriebe
  • Forstbetriebe, Sägewerke
  • Holzbau, Tischlerei, Holzkunst, Holzschnitzer
  • Kommunalwirtschaftliche Betriebe, die akkubetriebene Kleingeräte einsetzen
  • Herstellung akkubetriebener Kleingeräte
  • Alle Betriebe, die viele Akkus laden und vorhalten müssen
  • Individuelle Anforderung im Bereich Batterien mit mittlerer Leistung

Sind Sie in einem dieser Bereiche tätig? Suchen Sie nach einer professionellen und passenden Lösung für Ihre sichere Ladeinfrastruktur? Dann unterstützen wir Sie gerne bei Ihrem Vorhaben.

Kontakt

Safe handling of lithium batteries

Possible dangers from lithium batteries

With today's manufacturing standards, it can be assumed that lithium batteries are comparatively safe if handled properly and correctly.

However, if an uncontrolled and accelerated release of chemically stored energy occurs due to technical defects or improper handling, this usually takes the form of thermal energy, which can lead to a fire.

As a general rule, lithium batteries can be dangerous if they are operated or stored outside their specifications. Dangers result in particular from incorrect handling and improper use.

Kategorisierung Lithium-Batterien

Das Gefährdungspotential von Lithium-Batterien wird, neben dem Produktdesign, maßgeblich durch die Leistung der Module bzw. des Systems selbst bestimmt.

Bei den derzeit bekannten Typen bietet sich zur Differenzierung eine Unterteilung in drei Kategorien an (siehe Abbildung):

  • Lithium-Batterien geringer Leistung: Hierzu zählen alle einzelligen Batterien und Kleinbatterien, welche vornehmlich für den Bereich Computer, Multimedia, Kleinelektrogeräte und Kleinwerkzeuge etc. verwendet werden.
  • Lithium-Batterien mittlerer Leistung: Batterien dieser Kategorie werden z.B. für Fahrräder mit elektrischem Hilfsantrieb (Pedelec, E-Bike), E-Scooter, Light Electric Vehicle, größere Gartengeräte, diverse Kleinfahrzeuge und dgl., aber auch als Zellen für Fertigung von Batterien hoher Leistung verwendet.
  • Lithium-Batterien hoher Leistung: Batterien dieser Kategorie sind durch eine besonders hohe Leistung gekennzeichnet, welche sich durch die Kombination und Verknüpfung von Zellen mittlerer Leistung zu einem System ergibt. Derzeit bekannte Einsatzgebiete sind vornehmlich Elektromobilität (Automotive) sowie netzunabhängige Großgeräte.

Kategorisierung Lithium-Batterien

Kategorisierung Lithium-Batterien (Quelle: VdS 3103:2019-06)

Allgemeine Sicherheitsregeln

  • Einhaltung aller Vorgaben der jeweiligen Hersteller und technischer Produktdatenblätter
  • Verhinderung äußerer Kurzschlüsse (Schutz vor Kurzschluss der Batteriepole, z.B. durch Verwendung von Polkappen)
  • Verhinderung innerer Kurzschlüsse (Schutz vor mechanischen Beschädigungen)
  • Nicht unmittelbar und dauerhaft hohen Temperaturen oder Wärmequellen aussetzen.
  • In nicht durch automatische Löschanlagen geschützten Bereichen ist eine bauliche oder räumliche Trennung von mindestens 2,5m zu anderen brennbaren Materialien einzuhalten
  • Beschädigte oder defekte Lithium-Batterien sind aus Lager- und Produktionsbereichen umgehend zu entfernen und bis zur Entsorgung in sicherem Abstand oder in einem brandschutztechnisch abgetrennten Bereich zwischenzulagern
  • Es dürfen nur Batterien gelagert werden, für die der Nachweis der Prüfung nach UN38.3 vorliegt.

Spezifische Sicherheitsregeln für Lithium-Batterien mittlerer Leistung

  • Bereiche mit Batterien mittlerer Leistung sind von anderen Bereichen räumlich (mindestens 5m) oder baulich feuerbeständig abzutrennen.
  • Mischlagerungen mit anderen Produkten, die einen Brand beschleunigen können, sollten vermieden werden.
  • Der Lagerbereich ist durch eine geeignete Brandmeldeanlage mit Aufschaltung auf eine ständig besetzte Stelle zu überwachen.
  • Bei Vorhandensein von Feuerlöschanlagen sind die Angaben in Bezug auf geeignete Löschmittel in den jeweiligen technischen Produktdatenblättern zu berücksichtigen.
  • Bei größeren Lagermengen (belegte Flächen >60m² und/oder Lagerhöhe > 3m) gelten die Hinweise für Lithium-Batterien hoher Leistung.

Spezifische Sicherheitsregeln für Lithium-Batterien hoher Leistung

Für Batterien hoher Leistung liegen nach derzeitigem Stand noch keine gesicherten Kenntnisse hinsichtlich adäquater Schutzmaßnahmen vor. Schutzmaßnahmen sind daher in Absprache mit dem Sachversicherer für den Einzelfall zu regeln.

Denkbare Maßnahmen sind:

  • Separierung und Mengenbegrenzung
  • Lagerung in feuerbeständig abgetrennten Bereichen oder mit Einhaltung eines Sicherheitsabstandes (räumliche Trennung von 5m)
  • Automatische Löschanlage

Die spezifischen Sicherheitsregeln für Lithium-Batterien hoher Leistung stellen keinen Anwendungsfall für unsere Ladecontainer dar.

System description

Equipment and individual extensions

Begehbares Brandschutzlager

Begehbares Brandschutzlager

  • Begehbares REI 90/F 90 Brandschutzlager
  • DIBt-Zulassung (Deutsches Institut für Bautechnik)
  • Bemaßung Außen BxTxH (ohne Anbauten) = 2,82 m x 2,58 m x 2911 m
  • Weitere Tiefen in Schritten von jeweils 1,20 m möglich
  • Flexible Innen- oder Außenaufstellung auf einer Betonfläche
  • Feuerverzinkte Auffangwanne
  • Anti-Panik Brandschutztür
  • RAL 9002 Grauweiß

Grundausstattung Ladecontainer

Grundausstattung Ladecontainer

  • Brandschutzsystem (Multisensormelder, Esserbus Koppler)
  • Not-Aus Taster und Signalsäule
  • Beleuchtung und Servicesteckdose
  • Klimatisierung (Sommer +20°C; Winter +5°C)
  • Technische Lüftung
  • Steuerschaltschrank
  • Kundenschnittstelle 16A Schutzkontaktsteckdosen

Optionale Ausstattung Ladecontainer

Optionale Ausstattung Ladecontainer

  • Automatische Türfeststellanlage
  • Überwachung Raumtemperatur
  • Türpositionsschalter
  • Zusätzlicher Not-Aus Schalter im Eingangsbereich
  • Bewegungsmelder
  • Überwachung jedes einzelnen Ladevorgangs (intelligente Steckdosen)

Security concepts

Three different security classes

General

Ladecontainer für Akkus
  • Certified fire protection storage that can withstand a fire inside or outside the container for at least 90 minutes
  • External marking and labeling in accordance with all legal requirements
  • Active ventilation
  • Air conditioning (heating & cooling)
  • Entrance door with panic lock
  • Power supply via lockable terminal box on the outside of the charging container
  • Main switch on the control cabinet

SafetyClass-Basic

  • Abschalten der Steckdosen über Sicherheitsrelais
  • Überwachte Sicherheitsfunktionen sind Rauchmelder und Not-Aus-Taster
  • Überwachung Raumtemperatur
  • Statusanzeige Ladecontainer per Signalsäule
  • Einhaltung der aktuellen gesetzlichen Anforderungen hinsichtlich Arbeits- und Brandschutzverordnung

SafetyClass-Basic

SafetyClass-Advanced

  • Grundfunktion wie bei Variante Basic
  • Zusätzliche Signalverarbeitung mit einer SPS
  • Zusätzliche Sicherheitsüberwachung jedes einzelnen Ladevorgangs
  • Zusätzliche Sicherheitsüberwachung von Temperaturen
  • Abschaltung einzelner Ladevorgänge bei Abweichungen zum Normalbetrieb
  • Statusanzeige auf 12“ HMI

SafetyClass-Advanced

SafetyClass-Advanced-Pro

  • Grundfunktion wie bei Variante Advanced
  • Zusätzliche Integration vom Circlesystem
  • Benutzung über webbasierte Oberfläche möglich / Erstellung individueller Dashboards
  • Realtime Datenanalyse
  • Bereitstellung von Reports
  • Benachrichtigung des Betreibers bei Warnungen oder Alarme per E-Mail oder SMS möglich

SafetyClass-Advanced-Pro

Our service

For the realization of your charging infrastructure

Thanks to the experience we have gained in recent years and our regular exchanges with customers, we have been able to build up specialist expertise in the field of charging containers for medium-capacity batteries.

Together with our knowledge from over 30 years of special machine construction in the field of automation, we offer an excellent basis for the realization of new projects.

Unser Service umfasst folgende Leistungen:

  • Individuelle Konzepterstellung für Ihren Ladecontainer
  • Vorvermessung und Aufnahme der wichtigen Ladeparameter der von Ihnen verwendeten Ladegeräte und Akkus
  • Individuelle Anpassung des Lademanagementsystems je nach Kundenanforderung
  • Montage, Transport, Installation und vor Ort Inbetriebnahme der Ladecontainer
  • Unterweisung in die sichere und fachgerechte Benutzung der Ladecontainer
  • Circle Schulung für die Benutzung und Auswertung des Lademanagementsystems
  • Bereitstellung von Mietservern
  • Jährliche Sicherheitsunterweisung in Bezug auf Warnhinweise, Sicherheitskennzeichnung, Verhalten im Fehlerfall, sicherer Umgang mit Li-Ionen Batterien und vieles mehr
  • Wiederkehrende Sicherheitsüberprüfung der Ladecontainer nach DIN VDE 0105-100 inkl. Software- und Firmwareupdates
  • Wiederkehrende Container Inspektion
  • Wiederkehrende Überprüfung der Ladegeräte nach DGUV Vorschrift 3
  • Wartung und Instandhaltung der Ladecontainer

Kontakt

Haben wir Ihr Interesse geweckt?

Auf der Suche nach einem sicheren System für Ihre vorhandenen Ladegeräte, oder der Realisierung einer neuen Ladeinfrastruktur (bis zu 384 Akkus pro Ladecontainer), beraten wir Sie sehr gerne und unterstützen Sie bei der Umsetzung.

Volker Geißler

Volker Geißler
Product Manager

volker.geissler@clausohm.de
+49 241 9278819 2
+49 173 2443042

FAQ

Frequently asked questions

Do I need building or other permits?

No, planning permission and other permits are not required. A sufficiently large area is sufficient to set up the loading container.

What preparation is required to set up the battery charging container?

No foundation is required and the installation location is flexible. A solid surface is sufficient for setting up the loading container.

Are there any distances to be maintained?

No special requirements apply to the loading container with regard to the minimum distances to be maintained. The general regulations of the respective state building regulations apply. Furthermore, a service distance of at least 1 meter from adjacent buildings or facilities is recommended.

What are the special features of the loading container?

The loading container has an intelligent loading management system that includes the following key points:

  • Active load management
  • Integrated safety functions (fire alarm system, emergency stop button)
  • Temperature monitoring
  • Detection of defective accumulators
  • Detection and display of the charging status
  • Loading capacities
  • Expandability with additional loading options in the container
How many batteries can be charged at the same time?

The maximum number of charging processes depends on the charging currents of the chargers or batteries used. You can charge up to 150 batteries at the same time.

What security systems does the loading container have?

The loading container has a smoke detection system, temperature monitoring, an emergency stop switch inside and outside the container, active ventilation and a panic lock.

How long does the delivery take?

The current delivery time including delivery, installation and commissioning is 22 to 25 weeks.

Where is the container developed and built?

The container was developed in Germany and is also built in Germany.

What is the power consumption?

The input power is up to 100 KW.

What are the dimensions of the container?

The container measures 3.30 meters high, 2.80 meters wide and 3.50 meters long. The container weighs 3 tons.

Does the container comply with current guidelines?

The container complies with the F90 and CE directives.

Can I check the current status externally?

Yes, you can view the measurement data via a web-based dashboard.

Regulations

Building law and technical requirements for the loading container

  • DIN IEC/TS 62840-1 (VDE V 0122-40-1): 2017-06 Battery swap systems for electric vehicles - Part 1: General and guidance (IEC/TS 62840-1:2016)
  • DIN EN IEC 62840-2 (VDE 0122-40-2): 2019-08 Battery changing systems for electric vehicles - Part 2: Safety requirements (IEC 62840-2:2016);
    German version EN IEC 62840-2:2019
  • Building regulations for the state of North Rhine-Westphalia (Landesbauordnung 2018 - BauO NRW 2018)1
  • Charging station ordinance (LSV) - Ordinance on minimum technical requirements for the safe and interoperable installation and operation of publicly accessible charging points for electric vehicles
  • VdS 3103:2019-06 (03) Publication of the German insurers (GDV e.V.) for damage prevention Lithium batteries
  • The German Standardization Roadmap for Electromobility - Version 3.0
  • TRGS 800 (Technical rules for hazardous substances) Fire protection measures
  • TRBS 3151/ TRGS 751 (Technical rules for operational safety/hazardous substances) Prevention of fire, explosion and pressure hazards at filling stations and gas filling systems for filling land vehicles
  • German Industrial Safety Ordinance (BetrSichV) Ordinance on Safety and Health Protection in the Use of Work Equipment
  • DIN VDE 0100-704 Erection of low-voltage installations - Part 7-704: Requirements for special locations, rooms and installations - Construction sites
  • Safety concept for charging park from 12.05.2020 by Nowas Ingenieurbüro AF Ingenieur-Consult GmbH
  • BS-ST-RL-37-A-01-2018 dated 23.01.2019 Fire protection statement for the construction of a container charging station for lithium-ion batteries (Eddy-Roller) to the west of the existing building V23 on the premises of AWISTA GmbH Höherweg 222, 40233 Düsseldorf

1 The building regulations may differ depending on the federal state.